INSTALLATION
5-45
System 2 Installation / Programming Manual
Heavy-Duty RTE Button (p/n 4035) Use the following wire connections.
Normal Operation:
Green Set of Contacts (3 & 4) to #22 & #27
Lamp to #22 & #29
Green LED to #28 & 30
Fail Safe:
Red Set of Contacts (1 & 2) to #34 and Positive side of Magnetic Lock coil
Lamp to #22 & #29
Green LED to #28 & 30
Light-Duty RTE Button (p/n 4135) Use the following wire connections.
Normal Operation:
Green Set of Wires to #22 & #27
Green LED to #28 & 30
Fail Safe:
Blue Set of Wires to #34 and Positive side of Magnetic Lock coil
Green LED to #28 & 30