Myalarm Genesys 824 Alpha Especificaciones Pagina 9

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 22
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 8
3440-0241 Rev G
8
70 B Auxiliary Power Fault Report Code
(2 Digit Entry)
This code will be transmitted to the central station if the
auxiliary power fuse is open.
Value 01 - FF, Default: 00 (Disabled).
70 C Keypad Fire Report Code
(2 Digit Entry)
This code will be sent to the central station when "STAY AND
"6" are pressed simultaneously for approximately 2 seconds
then the buttons are released.
(see memory location 76A)
Value 01 - FF, Default: 00 (Disabled).
71 Keypad Emergency Report Code
This code will be sent to the central station when "INSTANT"
AND "9" are pressed simultaneously for approximately 2
seconds when the buttons are released.
(see memory location 76A)
Value 01 - FF, Default: 00 (Disabled).
71 A Keypad Panic Report Code
This code will be sent to the central station when "AWAY"
and "3" are pressed simultaneously for approximately 2
seconds when the buttons are released.
(see memory location 76A)
Value 01 - FF, Default: 00 (Disabled).
71 B Open Restore Report Code
(2 Digit Entry)
This report code will be transmitted when the system has
been disarmed after an alarm condition has been occurred.
Value 01 - FF, Default: 00 (Disabled).
71 C 2 Wire Smoke Detector Report Code
- (2 Digit Entry)
This report code will be transmitted to the central station
when the 2 wire smoke detector circuit senses an alarm
condition. (terminals 26 and 25).
Value 01 - FF, Default: 00 (Disabled).
72 Fire Trouble Report Code
(2 Digit Entry)
This report code will be transmitted to the central station
when a trouble is detected on the 2 wire smoke detector
loop.
Value 01 -FF, Default: 00 (Disabled).
72 A Fire Restore Code
- (2 Digit Entry)
This reporting function is a common restore code for both
Fire Alarm and Fire Trouble on the 2 wire smoke detector
circuit. This report code will be transmitted to the central
station after a fire alarm or fire trouble has been reset.
Value 01 - FF, Default: 00 (Disabled).
72 B Bell Restore Code
(2 Digit Entry)
This report code will be transmitted when the bell circuit has
reset and the zone has been secured after an alarm
condition. The code will not be transmitted until the zone is
secured , even though the bell circuit has reset.
Value 01 - FF, Default: 00 (Disabled).
72 C Ground Fault Report Code
(2 Digit Entry)
This report code will be transmitted to the central station
when the supervised earth ground is lost on the G-FM3.
(see memory location 76)
Value 01 - FF, Default: 00 (Disabled).
Memory Location 73 - 74
EXPANDERS, KEYPADS AND PARTITIONS
73 Expander Zone Definition
(2 Digit Entry)
This location determines the number of Expander Boards (G-
EX) that are installed. The choices are as follows:
00
- No zone expansion board on bus
01
- G-EX number 1 installed .
02
- G-EX number 1 & 2 installed .
03
- Not Used / Future Use
04
- Not Used / Future Use
05
- Not Used / Future Use
06
- Not Used / Future Use
07
- Not Used / Future Use
Default: (00) No Expansion Board
If you have selected this option without installing the
expander boards the keypad will indicate a "
Bus Failure"
trouble and transmit a Bus Fault report code. This G-EX(s)
must also be addressed by removing the appropriate
shorting links. (see wiring diagram) (see memory location
73B). Value 01 - 02, Default: 00 (Disabled).
73 A Keypad Installed/Partitions
- Requires depressing the
number that corresponds to the option that you wish to enable
will be displayed on the LCD. Depressing a number that
previously was displayed will remove the number from the LCD
and disable the option.
OPTIONS
1 = KEYPAD 1 Always ON
2 = KEYPAD 2
3 = KEYPAD 3
4 = KEYPAD 4
5 = KEYPAD 1 for partition 1
6 = KEYPAD 2 for Partition 1
7 = KEYPAD 3 for Partition 1
8 = KEYPAD 4 for Partition 1
One through four are enabling the number of keypads that
are going to be used.
Five through eight are assigning the keypads to a partition. If
the number is displayed, that keypad will be assigned to
partition number one. If the number is not displayed, that
keypad will be assigned to partition number two (see memory
location 76A).
73 B Buss Fault Report Code
(2 Digit Entry)
This report code will be transmitted to the central station if a
open or short is detected on the keypad buss.
Value 01 - FF, Default: 00 (Disabled).
73 C Charge Time - High & Low
(2 Digit Entry)
Add total current draw of the system including control panel,
keypad(s) and auxiliary devices. Use the following table to
get digits for location 73C.
Vista de pagina 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 21 22