3440-0241 Rev G
12
78 A Duress PIN
(4 Digit Entry)
This PIN will arm or disarm the system and will transmit the
duress report code (see memory location 68B) to the central
station.
Value 0000 - 9999, Default: BLANK.
NOTE
: PIN's (installer, duress, user) cannot be duplicated.
If a duplicate PIN is attempted to be programmed
an audible from the keypad will indicate the PIN
has been rejected.
79 - 79 A Battery Charging Calculations
BATTERY CALCULATIONS
To comply with UL requirements the primary power failure
trouble signal for the communicator shall not be
transmitted until the standby power capacity is at least 25
percent depleted, but not more than 50 percent.
Therefore, it is necessary to program these two memory
locations with the total current available (subtract total
current draw of panel, keypad(s), expansion modules and
other auxiliary devices powered from auxiliary power from
total current capacity) and amp-hour rating of battery to be
used.
79) 1000 mA - Total current in mA
10 = XX
Convert XX in Hex Chart 1 and enter in 79.
79 A) AH Batt x 10 = YY
Convert YY in Hex Chart 1 and enter in 79 A.
NOTE 1:
LOW BATTERY CODE is transmitted when:
1) there is no battery connected;
2) the battery fuse is open;
3) the battery voltage goes below approximately
11.5 VDC.
NOTE 2:
GOOD BATTERY is transmitted when the battery
voltage reaches approximately 12 VDC.
79B First 2 digits of Panel Access ID for RPU
(Remote Programming Utility)
79C Last 2 digits of Panel Access ID for RPU
Memory Location
80 - 95
NOT USED / FUTURE USE
ALPHA PROGRAMMING INSTRUCTION
The alpha programming of the control panel is accessed by
entering the
installers PIN
(
↑
↑↑
↑
) 7
&
(AWAY)
. The LCD will
change to:
ENTER ZONE #
.
The zone number you wish to program should be entered as
two digits (o1-24). Pressing the
(
↑
↑↑
↑
)
will lock in your selection
and the LCD will change to read:
ENTER ZONE #
ZONE ONE
(ZONE ONE was used only as an example)
At this point you may now begin entering the alpha text you
wish by selecting the number that corresponds to the letter or
character from the chart on page. You must press
(
↑
↑↑
↑
)
after
each of your selections to lock in the letter and this will
automatically advance the cursor to the next character. Once
editing of the zone name have been completed, you
must
press
(INST)
to lock your selection into memory. If
(INST)
is not
pressed, the name will revert to the factory default: settings.
After
(INST)
is pressed, the LCD will now request another zone
number be entered. Repeat the above procedure until all zones
have been named.
Once all zones have been named, press
(#)
once to return to
the main installers program mode. Pressing the
(#)
a second
time will return the User's operating mode.
PROGRAMMING HINTS
:
1)To enter a space, simply press the
(
↑
↑↑
↑
)
. The cursor will delete
the previous character (if anything) and advance to the next
character.
2) To move about the location without deleting the characters,
press
(AWAY)
to move right or press
(STAY)
to move left.
WIRING INSTRUCTIONS
TERMINALS
1 & 2 16 VAC Class II plug-in transformer (20 VA
maximum). Use 18 GA twisted or zip pair and keep
wire run as short as possible. Test the electrical
outlet being used to ensure it is not controlled by a
light switch. (24 hour source)
3-4-5-6 Data bus inputs - These terminals are used for
wiring in keypads (maximum 4), expansion modules
(maximum 2), and G-FM3. The keypads and
expansion modules can be wired in either a daisy
chain or homerun configuration. Each keypad must
be addressed by setting the two dip switches
located on the back of each keypad. Maximum
cable length 1,000 feet.