
3440-0241 Rev G19
SMOKE DETECTOR PLACEMENT
(Reprinted from NFPA-72 1993)
B-2 Smoke Detection.
B-2.1 Where to Locate the Required Smoke Detectors
.
B-2.1.1
The major threat from fire in a family living unit is at
night when everyone is asleep. The principal threat to
persons in sleeping areas comes from fires in the
remainder of the unit; therefore, smoke detector(s) are best
located between the bedroom areas and the rest of the unit.
In units with only one bedroom area on one floor, the
smoke detector should be located as shown in
Figure B-2.1.1.
Figure B-2.1.1
A smoke detector (indicated by cross) should be
located between the sleeping area and the rest of the family living
unit.
B-2.1.2
In family living units with more than one bedroom
area or with bedrooms on more than one floor, more than
one smoke detector will be needed, as shown in
Figure B-2.1.2
Figure B-2.1.2 In family living units with more than one sleeping
area, a smoke detector (indicated by cross) should be provided to
protect each.
B-2.1.3
In addition to smoke detectors outside of the
sleeping areas, this standard requires the installation of a
smoke detector on each additional story of the family living
unit, including the basement. These installations are shown
in Figure B-2.1.3. The living area smoke detector should be
installed in the living room and/or near the stairway to the
upper level. The basement smoke detector should be
installed in close proximitry to the stairway leading to the
floor above. If installed on an open-joisted ceiling, the
detector should be placed on the bottom of the joists. The
detector should be positioned relative to the stairway so as
to intercept smoke coming from a fire in the basement
before the smoke enters the stairway.
B-2.2 Are More Smoke Detectors Desirable?
The
location of the required smoke detectors does not provide
adequate protection for the occupants from a fire starting
within their bedrooms, nor do the required smoke detectors
provide reliable early warning protection for those areas
separated by a door from the areas protected by the
required smoke detectors. For these reasons, it is
recommended that the householder consider the use of
additional smoke detectors for those areas for increased
protection. The additional areas include: basement,
bedrooms, dinning room, furnace room, utility room, and
hallways not protected by required smoke detectors. The
installation of smoke detectors in kitchens, attics (finished
or unfinished), or in garages is not normally recommended
as these locations occasionally experience conditions
which may result in improper operation.
B-2.3 Smoke Detector Mounting - “Dead” Air Space.
B-2.3.1
The smoke from a fire generally rises to the ceiling,
spreads out across the ceiling surface and begin to bank
down from the ceiling. The corner where the ceiling and
wall meet is an air space into which the smoke may have
difficulty penetrating. In most fires, this “dead” air space
measures about 4 in. (0.1m) along the ceiling from the
corner and about 4 in. (0.1m) down the wall as shown in
Figure B-3.2.1. Detectors should not be placed in this
“dead” air space.
Figure B-2.1.3
A smoke detector (indicated by cross) should be
located on each story.
Figure B-3.2.1
Example of proper mounting for detectors.
FOR GRADE A LOCAL MERCANTILE INSTALLATIONS
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM
DINING KITCHEN
TV
ROOM
D R
L R
K B R
B R
BED
ROOM
Bedroom
Hall
Bedroom
Living
Room
Dining
Room
Basemen
τ
4
in
.
0.1
m
4 in. min.
(0.1 m)
12 in. max.
(0.3 m)
Top of
detector
Never
here
Acce
table
Ceiling
Side
wall
ΝΟΤΕ:
Measurements shown are to
the
closest edge of the detector
Comentarios a estos manuales