3440-0241 Rev G
9
TOTAL SYSTEM DIGIT TO ENTER
CURRENT (mA) IN LOCATION
73C
00 - 100mA 91
101 - 200mA 92
201 - 300mA 93
301 - 400mA 94
401 - 500mA 95
501 - 600mA 96
601 - 700mA 97
701 - 800mA 98
801 - 900mA 99
74 Abnormal Self Test Report Code
(2 Digit Entry)
This communicator test report code will be transmitted in place
of the self test code programmed in memory location 77C
should a fire zone or the two wire smoke detector loop be left in
an alarm or trouble condition .
NOTE:
This must be used to comply with UL864.
74A Telephone (TLM) Fault report code (2 Digit Entry)
This code will be sent whenever a telephone line fault is
detected. (See also memory location 76-6)
Value 00 - FF.Default: 00 (Disabled)
Memory Location 75 - 75C
SIGNAL ROUTING
75 Receiver Reporting for Alarm & Restores - Open &
Close
(2 Digit Entry)
If you have been assigned to only one telephone number and
account number, duplicate the receiver information and select
option 2 for memory locations 75 and 75A.
The first digit tells the panel which receiver or receivers to direct
the alarm and restore report codes.
Value 0 - 4, Default: 0.
Value Function
0 Report only to receiver number 1
1 Report only to receiver number 2
2 Report first to receiver number 1, If not successful,
attempt to report to receiver number 2
3-4 Report to receiver number 1 and receiver number 2
The second digit tells the panel which receiver or receivers to
direct the open and close report code to.
Value 0 - 4, Default: 0.
Value Function
0 Report only to receiver number 1
1 Report only to receiver number 2
2 Report first to receiver number 1, if not successful,
attempt to report to receiver number 2
3 Report to receiver number 1 and receiver number 2
4 No reporting for receiver number 1 or number 2
75 A System Report Code
(2 Digit Entry)
The first digit tells the panel which receiver or receivers to direct
the housekeeping signals (power codes, failure codes, keypad
triggered alarm codes, etc.).
Value 0 - 9, Default: 0.
Value Function
0 Report only to receiver number 1
1 Report only to receiver number 2
2 Report first to receiver number 1, if not successful,
attempt to report to receiver number 2
3 Report to receiver number 1 and receiver number 2
4 No Telco reporting for System messages
Value 0 - 4 Default: 0
The second digit selects reporting of codes on Long-range
radio.
Value Function
0 No radio out put for open/close, system test, or
system messages
1 open/close on radio
2 system test code on radio
3 open/close + system test codes on radio
4 system messages on radio
5 system message + open/close on radio
6 system message + system test on radio
7 system message + system test + open/close on
radio
Value 0 - 7 Default: 0
75 B Communication Fail Report Code
(2 Digit Entry)
The Communication Fail Report Code is transmitted when the
panel has exhausted its dialing attempts
(see memory location 53B).
Value 01 - FF, Default: 00 (Disabled).
Note
:
Must use "Two phone lines" or "One phone line and
Long range radio".
75 C Number of Radio Attempts
The number of times the event is transmitted via
Varitech
long
range radio.
Value 00 - 09 units Default: 00 (Disabled)
Memory Location 76 - 79C
SYSTEM FEATURES
76 System Features
(Multiple Entries) requires depressing
the number that corresponds to the option that you wish to
enable and the number will be displayed on the LCD.
Depressing a number that previously was displayed will remove
the number from the LCD and disable the option.
Shows Default condition : All OFF
OPTIONS
1 = Bell Test
2 = Bell Audible on Bus Fault
3 = Digital first & Radio second
4 = G-FM3 Installed
5 = 50 Hz
6 = Telephone Fault(TLm)Monitoring enable
7 = System test to be reported on Telco
8 = Partition System
1 - Bell Test
With this option selected, the bell voltage will
be present for three seconds when the control panel is
armed.
Default: NO
2 - Bell Audible on Bus Fault
With this option selected
the bell voltage will energize should the panel detect a fault