3440-0241 Rev G17
TO DEFAULT THE 824 CONTROL PANEL
1. Press [installer pin] + [
"
] + [7]
2. The display will read [PRG]
3. Press [99], The display will read [TST#]
4. Press [0], Display will read [DEF]
5. Press [
"
], Display will read [CODE]
6. Press [9999] then press [
"
]. Wait 15 seconds.
7. The display will flash [TIME]. The panel is now defaulted.
BUS TEST
This Procedure is to determine whether keypads and or add
on modules are functional. It is very helpful for trouble shooting
the system for failures of hardware.
[Installer PIN] + [
"
] + [7]
Keypad will display [INSTALLER PROGRM ENTER ITEM#]
Press [9] [9]
Keypad will display [TST#]
Press [1]
Keypad will display [WAIT]
Wait approximately 50 seconds.
Keypad will beep and display [BUS ERROR]
Note:
Do not touch keypad while beepin
g.
After keypad stops beeping press [
"
]
to view result of test.
If there is anything less than 45 should display, there is a
potential problem that might occur, such as keypad or module
failure indications.
Each depression of the [
"
] will advance the display to the next
programmed device.
the symbols for each device are;
[B1:--] = Keypad Number 1
[B2:--] = Keypad Number 2
[B3:--] = Keypad Number 3
[B4:--] = Keypad Number 4
[B9:--] = Expander Board 1
[BA:--] = Expander Board 2
[BB:--] = Fire Module (G-FM3)
TO EXTEND THE POWER OF PGM OUTPUT
The PGM output has a maximum current rating of 20mA.
If you are going to use the
PGM
outputs for triggering some
other control or indicating devices that draw more than 20mA
you must use a
RELAY MODULE
. Your local distributors carry
modules such as the
ALTRONIX RBSN
RELAY MODULES
and the
ALARM CONTROL CORP. MODEL 8007 RELAY
MODULE WITH THE 8012 RELAY
which are low current draw
relays
.
Maximum current on relay contacts depends on which
module is used.
NOTE:
After you have completed testing the systems cut
one side of the resistor on the 8007 relay module board,
this will allow the relay to operate at a lower voltage
should the AC POWER fail and the battery voltage gets
low. After cutting the resistor please test unit again.
Please note Fig.2
Figure 2
When using a
PGM
for
Ground Start,
use the wiring hook
up shown in Fig.3
Figure 3
Note:
The panel must be attached to either earth or cold
water pipe ground for proper ground start operation
.
Note:
When using a RBSN-TTL relay module. Tie the TRG
terminal on the RBSN-TTL module to the positive
voltage terminal 7 of the panel and use it just like a
RBSN module.
CNCNO
CNCNO
PGM
AUX
Pos.
EXT
P.S.
Indicating
device
CNCNO
CNCNO
PGM
AUX
Pos.
Ground on
panel
Tip or ring
+
-