Page 80
House Codes 1-16 Format
House Codes 1-16 can be configured to use the Standard (Preset Dim Command), Extended Code (Level Command), Lightolier's
Compose Mode, UPB (open transmission format), Lutron’s RadioRA transmission format, LEVITON Lighting (HLC), and
CentraLite transmission format.
HC 1 FORMAT: 5
LEVITON LIGHTING #=CHNG ↕
To change format for House Code 1, press the ' # ' key, and then use the arrow keys to scroll through the list of formats. Press the
' # ' key to select the desired format
. After selecting, press the down-arrow key to change format for the next House Code.
FORMAT NUMBER DESCRIPTION
STANDARD 0 Preset Dim Command (X-10, X-10 Pro, Leviton, PCS, etc.)
EXTENDED 1 Extended Code Level Command (Leviton)
COMPOSE 2 Compose Mode (Lightolier's Compose)
UPB 3 Universal Powerline Bus (open format)
RADIO RA 4 Lutron RadioRA
LEVITON LIGHTING 5 LEVITON Lighting Control (HLC)
CENTRALITE 6 CentraLite Lighting
VIZIA RF Z-WAVE 7 Vizia RF Z-Wave
The default setting for HC 1-16 Format is 5 (HLC).
House Codes 1-16 All Off
This feature allows you to choose if House Code 1-16 will respond to the “All Off” command. Press the 0 key to select “No” and
the 1 key to select “Yes”. After selecting, press the down-arrow key to change this option for the next House Code. The default
setting for HC 1-16 All Off is Yes.
HC 1 ALL OFF: 1
0=NO 1=YES ↕
Notes:
1. When configured, each House Code will affect 2 rooms of HLC or Vizia RF Z-Wave lighting (i.e. HC 1 ALL OFF affects
Room 1 and 2).
2. When the House Code is configured as UPB, RadioRA, or CentraLite, “House Code All Off” does not affect the state of the
installed devices; however, if this setup item is set to “Yes”, OmniPro II will change the status of all units on that House
Code to “Off” (even though it doesn’t explicitly send an All Off command to those units). If the “House Code All Off” setup
item is set to “No”, OmniPro II will not change the status of units on that House Code.
House Codes 1-16 All On
This feature allows you to choose if House Code 1-16 will respond to the “All On” command. Press the 0 key to select “No” and
the 1 key to select “Yes”. After selecting, press the down-arrow key to change this option for the next House Code. The default
setting for HC 1-16 All On is Yes.
HC 1 ALL ON: 1
0=NO 1=YES ↕
Notes:
1. When configured, each House Code will affect 2 rooms of HLC or Vizia RF Z-Wave lighting (i.e. HC 1 ALL ON affects
Room 1 and 2).
2. When the House Code is configured as UPB, RadioRA, or CentraLite, “House Code All On” does not affect the state of the
installed devices; however, if this setup item is set to “Yes”, OmniPro II will change the status of all units on that House
Code to “On” (even though it doesn’t explicitly send an All On command to those units). If the “House Code All On” setup
item is set to “No”, OmniPro II will not change the status of units on that House Code.